Serial I/O Modules for Monitoring and Control

Connect field signals to your PLC or gateway over RS485 Modbus RTU. Choose Y301 for digital I/O, mixed signals and 10 A relay control on ControlLink models, or Y331 for channel-isolated millivolt, voltage, milliamp and ampere inputs.

View Serial I/O Module Documentation
Y301 MiniLink, ControlLink, and FlexPoint serial I/O modules
  • Digital I/O
  • Modbus RTU
  • Multi-range AI

Define the field task first

What Do You Need to Monitor or Control?

Describe your signals and load. Then compare the input and output combination that fits your panel.

Y301-200 serial I/O module for equipment status monitoring

Monitor Equipment Status

Read switch, float and equipment status contacts from your controller. Choose a compact input model for a few points, or add relay control when the panel needs both.

Y301-200 · Y301-220 · Y301-440 · Y301-880Compare these models
Y301-440 serial I/O module for relay control

Switch Alarms, Valves and Contactors

Use Modbus commands to operate relay contacts. Check the selected model’s contact rating and use an external contactor when the load requires it.

Y301-020 · Y301-110 · Y301-220 · Y301-440Compare these models
Y301-444 serial I/O module with analog inputs

Read Sensors and Control Outputs

Bring analog measurements, digital status and relay control into one module. Choose two or four analog inputs for supported voltage or current signals.

Y301-222 · Y301-444Compare these models

Y331 Isolated Analog Inputs: More Signal Types

Acquire DC signals beyond standard 0–10 V and 4–20 mA. Choose 2, 4, 6 or 8 AI channels, each isolated from the other input channels.

Y331-0080 serial I/O module with eight isolated analog input channels

Millivolt inputs

0–100 mV · 0–500 mV

Voltage inputs

0–5 V · 0–10 V · 0–30 V

Milliamp inputs

0–20 mA · 4–20 mA

Ampere inputs

0–2 A · 0–10 A

Specify the input range when ordering. Connect each signal to its matching voltage or current terminals and keep each channel’s input pair separate.

Default communication: isolated RS485 with Modbus RTU. RS232 and isolated CAN are ordering options. Power: 6–36 VDC; screw mounting.

Y331-0020

2 isolated AI · 0 DI / 0 DO / 0 AO

Y331-0040

4 isolated AI · 0 DI / 0 DO / 0 AO

Y331-0060

6 isolated AI · 0 DI / 0 DO / 0 AO

Y331-0080

8 isolated AI · 0 DI / 0 DO / 0 AO

Select the range and channel count together. The 0–10 A option is a DC current input range; these Y331 models have no relay outputs.

Y301 Modbus RTU I/O Modules with 10 A Relay Outputs

Combine digital status monitoring and relay control over RS485 Modbus RTU. ControlLink models provide SPDT relay contacts rated at 277 VAC 10 A or 28 VDC 10 A.

Y301-222 and Y301-444 also include analog inputs. Match contact voltage, load type, steady current and inrush current before selection. Inductive loads may need protection and an external contactor. MiniLink relay ratings differ.

Built for your control panel

One serial link, the I/O combination your panel needs

Connect over Modbus RTU

Read inputs and control relay outputs from a compatible RS485 Modbus RTU master.

Choose the I/O You Need

Pick one or two digital points, expand to eight inputs and eight relay outputs, or combine digital I/O with analog sensing.

Acquire More AI Signal Types

Y331 offers millivolt, voltage, milliamp and ampere input ranges, with input channels isolated from one another.

Add Local Control Rules

ControlLink models support local relay rules; Y301-222 and Y301-444 also support analog threshold rules.

Compare Models

Connect field I/O to a serial Modbus host

A Serial I/O module sits between field signals or loads and the PLC, SCADA system, or edge controller that reads and writes its registers.

Y301 field I/O and Modbus control pathsCyan paths show input states and values moving from field I/O through a Y301 module to the Modbus host. Orange paths show relay commands moving from the host through the Y301 module to a field load.

Y301-444 shown as an example. Cyan: inputs and values to the host. Orange: relay commands to the field load. I/O count and signal support depend on the model.

  1. 01

    Signal and load sideConnect compatible inputs to DI or AI, and relay outputs to the selected load circuit.

  2. 02

    Module roleThe module exposes field states and values to the host and receives relay commands; it does not replace the controller.

  3. 03

    Host sideMatch the interface, protocol mode, baud rate, address, and register map.

Pick the I/O task, then compare channel count and electrical limits

MiniLink, ControlLink, and FlexPoint organize the Y301 range by I/O combination and project task.

Y301-110 compact MiniLink serial I/O module

MiniLink Family

Compact one- or two-channel digital I/O for status monitoring and relay control.

Best fit
  • Space-constrained panels
  • Simple DI or relay DO tasks

Y301-110 · Y301-200 · Y301-020

View MiniLink Models
Y301-444 ControlLink serial I/O module with mixed I/O

ControlLink Family

Combined digital input and relay output, with analog input and local rules on selected models.

Best fit
  • Monitoring and relay control in one module
  • Mixed digital and analog input requirements

Y301-220 · Y301-222 · Y301-440 · Y301-444 · Y301-880

View ControlLink Models
Y301-00G FlexPoint 16-channel analog input module

FlexPoint Family

Dedicated DI, AI, or AO modules for higher channel counts and signal-specific expansion.

Best fit
  • Six, eight, or sixteen input channels
  • Four, six, or eight analog output channels

Y301-600 · Y301-800 · Y301-G00 · Y301-006 · Y301-008 · Y301-00G · Y301-0004 · Y301-0006 · Y301-0008

View FlexPoint Models

Wiring patterns

Match the module to the signal and load

Use these three wiring patterns to identify the right product family. Final selection still depends on signal range, load, interface, supply, and installation conditions.

More Y301 I/O combinations

Need dedicated digital input, analog input or analog output? Open the complete range and compare all 17 models by I/O, power, interface and signal limits.

Compare All 17 Y301 Models

Includes 9 additional dedicated digital input, analog input and analog output models. Compare the I/O combination, then contact us to confirm model-specific limits before ordering.

9 models

FlexPoint

Dedicated DI, AI, or AO modules for higher channel counts and signal-specific expansion.

Open detailed comparison
ModelI/OPowerInterface / protocolSignal or load boundaryBest forAction
Y301-1101 DI + 1 relay DO5–36 VDCRS485; optional RS232 / TTL · Modbus RTUSPDT relay · 125 VAC 0.5 A / 30 VDC 2 AOne status input and one relay-control point
Y301-2002 DI5–36 VDCRS485; optional RS232 / TTL · Modbus RTUDry / wet contact · 5–36 V wet-contact · opto-isolatedTwo-channel status monitoring
Y301-0202 relay DO5–36 VDCRS485; optional RS232 / TTL · Modbus RTUSPDT relays · 125 VAC 0.5 A / 30 VDC 2 ATwo relay-control points
Y301-2202 DI + 2 relay DO5–36 VDCRS485; optional RS232 / TTL · Modbus RTU277 VAC 10 A / 28 VDC 10 A relays · up to 4 local rulesCompact monitoring and relay control
Y301-2222 DI + 2 relay DO + 2 AI5–36 VDCRS485; optional RS232 / TTL · Modbus RTU277 VAC 10 A / 28 VDC 10 A relays · 0–10 V / 4–20 mA AI · 16-bit · ±1% FS · up to 4 rulesMixed digital and sensor monitoring
Y301-4404 DI + 4 relay DO5–36 VDCRS485; optional RS232 / TTL · Modbus RTU277 VAC 10 A / 28 VDC 10 A relays · up to 8 local rulesFour-point monitoring and control
Y301-4444 DI + 4 relay DO + 4 AI5–36 VDCRS485; optional RS232 / TTL · Modbus RTU277 VAC 10 A / 28 VDC 10 A relays · 0–10 V / 0–5 V / 4–20 mA AI · 16-bit · ±1% FS · up to 8 rulesMixed four-channel monitoring and control
Y301-8808 DI + 8 relay DO5–36 VDCRS485; optional RS232 / TTL · Modbus RTU277 VAC 10 A / 28 VDC 10 A relays · up to 16 local rulesHigher-density digital monitoring and control
Y301-6006 DI7–30 VDCRS485 / RS232 · Modbus RTU / ASCIIOpto-isolated DI · 3.3–24 VDC active inputSix digital status points
Y301-8008 DI7–30 VDCRS485 / RS232 · Modbus RTU / ASCIIOpto-isolated DI · 3.3–24 VDC active inputEight digital status points
Y301-G0016 DI7–30 VDCRS485 / RS232 · Modbus RTU / ASCIIOpto-isolated DI · 3.3–24 VDC active inputSixteen digital status points
Y301-0066 AI7–30 VDCRS485 / RS232 · Modbus RTU / ASCII0–10 V / 4–20 mA · 12-bit · ±0.5% FSSix analog measurement points
Y301-0088 AI7–30 VDCRS485 / RS232 · Modbus RTU / ASCII0–10 V / 4–20 mA · 12-bit · ±0.5% FSEight analog measurement points
Y301-00G16 AI7–30 VDCRS485 / RS232 · Modbus RTU / ASCII0–10 V / 4–20 mA · 12-bit · ±0.5% FSSixteen analog measurement points
Y301-00044 AO12–30 VDCIsolated RS485; optional RS232 · RTU / ASCII0–10 V / 4–20 mA · 14-bit · ±0.1% FSFour analog setpoint outputs
Y301-00066 AO12–30 VDCIsolated RS485; optional RS232 · RTU / ASCII0–10 V / 4–20 mA · 14-bit · ±0.1% FSSix analog setpoint outputs
Y301-00088 AO12–30 VDCIsolated RS485; optional RS232 · RTU / ASCII0–10 V / 4–20 mA · 14-bit · ±0.1% FSEight analog setpoint outputs

Need help choosing? Tell us your application.

Look beyond the channel count

The correct model depends on the signal, electrical load, host connection, power, environment, and local-control requirement.

  1. 01

    Signal direction and type

    Identify each DI, relay DO, AI, or AO point and whether the signal is digital, voltage, or current.

  2. 02

    Channel count

    Count the required points and allow only the project margin you can justify.

  3. 03

    Range or load

    Verify analog range or relay operating voltage, steady current, inrush current, and load type.

  4. 04

    Host interface and protocol

    Check RS485, RS232, or TTL availability and the required Modbus mode for the selected model.

  5. 05

    Power and environment

    Note supply voltage, temperature, humidity, enclosure, wiring, and installation clearance.

  6. 06

    Local rules and accessories

    Confirm whether local rules, retention, converters, termination, protection, or external contactors are required.

Ready for the next step?

Wiring, Setup and Documentation

Check signal limits, terminal wiring and Modbus registers for the selected model before final design or ordering.

FAQ

Questions that change model selection. Check the product family, signal type, communication option, load, and required documents before final selection.

Which Modbus RTU I/O modules have 10 A relay outputs?

Y301-220, Y301-222, Y301-440, Y301-444 and Y301-880 provide RS485 Modbus RTU and SPDT relay contacts rated at 277 VAC 10 A or 28 VDC 10 A. The rating does not apply to every Y301 model. Verify load type, inrush current and protection requirements; an external contactor may be needed.

Can Y331 measure different analog signal types on isolated channels?

Y331-0020/0040/0060/0080 offers millivolt, voltage, milliamp and ampere input range options. Each input channel is isolated from the other input channels. Choose the range when ordering and use the corresponding voltage or current terminals. Mixed ranges and switching between ranges require confirmation for the ordered configuration. The 0–10 A range measures DC current; these models have no relay outputs.

How do I choose between Y301 and Y331 Serial I/O modules?

Choose Y301 for digital inputs, relay control, mixed I/O or dedicated DI, AI and AO expansion. Choose Y331-0020/0040/0060/0080 for 2, 4, 6 or 8 isolated analog inputs with millivolt, voltage, milliamp or ampere range options. Compare the signal range and electrical limits before choosing the channel count.

How do I choose between DI, DO, AI, and AO models?

Use DI for discrete status signals, relay DO for on/off load control, AI for supported voltage or current measurements, and AO for supported voltage or current setpoints. Verify signal range, common wiring, isolation, accuracy, and load requirements in the selected model specification.

Which serial interfaces and Modbus modes are available?

RS485 Modbus RTU is available across the documented Y301 family and is the default interface for these Y331 analog input models. Y331 also offers RS232 or isolated CAN interface options; specify the interface when ordering. RS232, TTL, and Modbus ASCII are available only on selected models. Set the host interface, protocol mode, baud rate, address, and register map for the selected model.

Can relay outputs switch pumps, motors, or other inductive loads directly?

Do not select a relay from steady current alone. Check operating voltage, inrush current, switching frequency, and load type. Y301-110 and Y301-020 are rated at 125 VAC 0.5 A or 30 VDC 2 A. The featured ControlLink models are rated at 277 VAC 10 A or 28 VDC 10 A. Inductive loads may require protection and an external contactor.

What information is needed for a model recommendation?

Share the I/O type and channel count, signal range or load, host interface and protocol, supply voltage, installation environment, and any local rule requirement. Submit the conditions you know; missing details can be filled in later.

Where can I find wiring diagrams, register maps, and manuals?

Open the detailed comparison above and follow the selected model specification for electrical and mechanical limits. Use the linked technical reference for wiring, configuration, communication settings, and register information.

Do you offer analog output or higher input-count models?

Yes. Open the full model comparison for dedicated 6-, 8-, or 16-channel digital input modules, 6-, 8-, or 16-channel analog input modules, and 4-, 6-, or 8-channel analog output modules. Their supply ranges and signal specifications differ from the featured models.

Tell Us Your Application

What do you need to monitor or control? Tell us about your signals and controller. We’ll help you choose a suitable Y301 or Y331 model — no model number needed.

  • I/O type and channel count
  • Signal range or controlled load
  • Host interface and protocol
  • Supply voltage and installation environment